TS200 IE 24/48/230 input extensions |
Description
The IE24 Input extension module has eight digital inputs; IE48 and IE230 have four digital inputs. Up to 7 extension modules (IE and/or OE) can be connected to one input- or output module (IM or OM). The digital inputs are wired on a terminal block.View

(2) Socket for terminal blocks
(3) Green LED lights when input active
(4) Labelling strip
(5) Connection to next module
Schematic

All inputs have a common 0V connection (GND) and are galvanically isolated from the logic of the module.

The inputs are both galvanically isolated from each other and from the logic of the module.

The inputs are both galvanically isolated from each other and from the logic of the module.
Technical data
IE24 |
IE48 |
IE230 |
Digital inputs (IEC1131-2) Input voltage: Signal = 0 Signal = 1 Limits Frequency at AC Typical input current Typical input resistance, Sensor connecting cable Shielding |
8 Less than +5 VDC) Greater than +14 VDC -36 .. +36 VDC 6 mA typ. 3.9 kOhm max. 100 m Not required |
4 Less than 30 VAC Greater than 70 VAC 265 VAC 50/60Hz 3.5 mA typ. 70 kOhm max. 100 m Not required |
4 Less than 2 VAC/VDC 12 - 48 VAC/VDC 0-55 VAC / -55 - +55 VDC 50/60Hz 18 mA typ. 2 kOhm max. 100 m Not required |
Power consumption, logic |
100 mW | 100 mW | 100 mW |
Electrical isolation Input / Logic and bus Input / Input |
yes no |
yes yes |
yes yes |
Ambient temperature Operating Storage |
0 to +55 °C -25 to +70 ° |
0 to +55 °C -25 to +70 ° |
0 to +55 °C -25 to +70 ° |
Protection category |
IP 40 | IP 40 | IP 40 |
Dimensions (W x H x D)in mm | 55 x 58 x 85 | 55 x 58 x 85 | 55 x 58 x 85 |
Weight |
120 g | 120 g | 120 g |