Description Programming Technical data Schematic Dimensions Order overview Downloads Link to predecessor model AS-D16 |
||
Operation-/Fault indicator LSE-D16 |
LSE-D16-BS Description
The LSE-D16-BS is an operation/fault indicator with 16 channels for front assembly.It includes integrated controls for horn acknowledgment, alarm acknowledgment and lamp test.
The built-in buzzer can be turned off. Each input (operation and fault input) can be switched separately between an opening contact and a closing contact.
A time delay can be activated collectively for all fault inputs. The indicator process of the fault can be choosen between new value or first-up indication.
The automatic alarm acknowledgment after energising the unit is activatable. It is also selectable if the operation LEDs shall be shown or suppressed during a fault condition.
The LSE-D16-BS has three potential free relay outputs which are defined as horn output until horn acknowledgement, common output and lamp test in the factory settings.
The output function can be changed with the programming to 'horn acknowledgement activated during keystroke on HQ', 'lamp acknowledgement activated during keystroke on LQ' and 'collective output priority 2'. The labelling is simply done with slide-in paper strips.
The connection is done using the plug-in screw terminals on the back of the unit.
The LSE-D16 operation/fault indicator is the replacement for the AS-D16 . The functionality and size are identical
LSE-D16-BS Programming
The programming of the LSE-D16-BS is carried out either with the web interface or the buttons in the front of the unit.View of the programming in the WEB interface:
The use of the web interface is described in a separate documentation, see Downloads
The parameterisation with the buttons on the front panel of the LSE-D16-BS has 6 programme levels:
1. Fault indicator inputs (red): Opening contact/closing contact switchover
2. Operating inputs (green): Opening contact/closing contact switchover
3. Virtual DIP switch: time delays, buzzer on/off, automatic acknowledgement and output modes
4. Activation of the LT output as common output priority 2
5. RGB colour setting of the fault inputs
6. RGB colour setting of the operation inputs
Levels 4 to 6 are deactivated when delivered. They can be activated in level 3 with DIP switch 16.
Technical data
Descripion | LSE-D16-BS Operation-/Fault indicator |
---|---|
Part number | LSE-D16-24-BS |
Communication | 16 Multicolour-LEN / integrated Buzzer |
Operation inputs | 16 inputs NO/NC each input separate |
Fault inputs | 16 inputs NO/NC each input separate / Time delay global |
Time delay fault inputs | 5s/10s/60s for all fault inputs, global |
Automatic alarm acknowledgement after energising | 5s/10s/60s for all fault inputs, global |
System imputs | External Horn acknowledgement / External Lamp acknowledgement / External Lamp test |
System outputs factory settings | Horn until HQ / Common / Lamp test activated for 5s |
Outputs alternative | Horn acknowledgement activated during keystroke on HQ / Lamp acknowledgement activated during keystroke on LQ / Common Priority 2 |
Switching capacity output relays | 6A 30VDC / 6A 250VAC |
Front control elements | Horn acknowledgement / Lamp acknowledgement / Lamp test |
Supply voltage | 8-30VDC / 12-28.5VAC, 40-80Hz |
Signal voltage | 24V AC/DC ± 20% |
Power consumption | Max. 3W |
Weight | 260g |
Dimensions | WxHxD 72x144x75mm |
Front panel cut out | 138x68mm |
Connectors, Plug-in screw terminals 0.2 - 2.5mm2 | |
Mounting position | Any |
Protection degree housing | IP40 |
Protection degree conntector | IP20 |
Temperature range | 0°C to 65°C |
Schematic
Dimensions
H | B | H1 | B1 | ET | T1 | T2 |
---|---|---|---|---|---|---|
144 mm | 72 mm | 136 mm | 65 mm | 75 mm | 52 mm | 8.5 mm |
Order overview
Order number | Designation | Appendage | Stock*1 | Price*2 | ||
---|---|---|---|---|---|---|
LSE-D16-BS | Operation/faultindicator 24V DC/AC | 2x 16 inputs, multicolour LED | 12 | 485.00 CHF |
*1: Stock levels are for reference only. The handout is done upon incoming orders. |
*2: Prices are uncommitted, errors are excepted. |