    The LSE Indicator Unit is designed to signalise the operation or fault of technical equipment. The wide range of applications reaches from simple machine displays up to signalising of technical alarms in buildings. The units are front mounted in a standard cut out. All electrical connections are realised by plug-in screw terminals on the back of the unit. Therewith, unit changes and mensurations are easily to realise. To build larger systems with a higher amount of inputs than a single device offers, it is possible to connect up to twelve units. The Indicator Unit is available with 8 or 16 inputs/LED's. Different colours, DUO-LED's and customer specific colour combinations are obtainable. The signal- and supply voltage is 24VDC.

    Function

    Signal inputs
    The 8 or 16 inputs are all NO normally open

    LED
    The LED's on the front are working as an image of the signal inputs

    Lamp test
    The lamp test button activates all LED's for about 4 seconds. If several units are connected together the lamp test is overlapping.






    Function diagram


    LSE Indicator unit






    Schematic


    Please click on the image for a larger view or go to the download of the wiring diagram sheet

    Indicator Unit with 8 Inputs / single colour LED's
    LSE

    Indicator Unit with 16 Inputs / single colour LED's
    LSE

    Indicator Unit with 8 Inputs / DUO-LED's
    LSE

    Indicator Unit with 16 Inputs / DUO-LED's
    LSE






    Programming


    The indicator unit does not need any programming




    Dimensions

    LSE Massbild

    H B H1 B1 ET T1 T2
    144 mm 72 mm 136 mm 65 mm 130 mm 108 mm 8.5 mm





    Technical data

    Number of inputs 8 / 16
    Type of inputs NO normally open
    Supply voltage 24-28VDC
    LED colours Red/green/yellow/DUO red-green/ Special colours and mixed on request
    Power consumption per LED max. 10mA
    Ambient temperature -20 - +65°C
    Mounting position Any
    Protection class Housing: IP40 / Terminals: IP20
    Connectors Plug-in screw terminals 4mm2 (2x1.5mm2)
    Weight 400g / 440g
    Dimensions WxHxD 144x72x130mm
    Front panel cut-out 138x68mm








    Order overview standard units

    Part number Image Description Shop
    LSE08-911.120 LSE Störmelder 8 LED red / 24VDC / with button LT
    LSE08-911.140 LSE Störmelder 8 LED yellow / 24VDC / with button LT
    LSE08-911.150 LSE Störmelder 8 LED green / 24VDC / with button LT
    LSE08-911.190 LSE Störmelder 8 DUO-LED red-green / 24VDC / with button LT
    LSE16-911.120 LSE Störmelder 16 LED red / 24VDC / with button LT
    LSE16-911.140 LSE Störmelder 16 LED yellow / 24VDC / with button LT
    LSE16-911.150 LSE Störmelder 16 LED green / 24VDC / with button LT
    LSE16-911.190 LSE Störmelder 16 DUO-LED red-green / 24VDC / with button LT