| Descripion | LSE-D16-BS Operation-/Fault indicator |
|---|
| Part number | LSE-D16-24-BS |
|---|
| Communication | 16 Multicolour-LEN / integrated Buzzer |
|---|
| Operation inputs | 16 inputs NO/NC each input separate |
|---|
| Fault inputs | 16 inputs NO/NC each input separate |
|---|
| Delay times for fault inputs with virtual DIP switch | 5s/10s/60s for all fault inputs collectively |
|---|
| Delay times for fault inputs with web interface | 1s to 48h for each fault input separately |
|---|
| Time delay fault inputs | 5s/10s/60s for all fault inputs, global |
|---|
| Automatic alarm acknowledgement after energising | 5s/10s/60s for all fault inputs, global |
|---|
| System imputs | External Horn acknowledgement / External Lamp acknowledgement / External Lamp test |
|---|
| System outputs factory settings | Horn until HQ / Common / Lamp test activated for 5s |
|---|
| Outputs alternative | Horn acknowledgement activated during keystroke on HQ / Lamp acknowledgement activated during keystroke on LQ / Common Priority 2 |
|---|
| Switching capacity output relays | 6A 30VDC / 6A 250VAC |
|---|
| Front control elements | Horn acknowledgement / Lamp acknowledgement / Lamp test |
|---|
| Supply voltage | 8-30VDC / 12-28.5VAC, 40-80Hz |
|---|
| Signal voltage | 24V AC/DC ± 20% |
|---|
| Power consumption | Max. 3W |
|---|
| Weight | 260g |
|---|
| Dimensions | WxHxD 72x144x75mm |
|---|
| Front panel cut out | 138x68mm |
|---|
| Connectors | Plug-in screw terminals 0.2 - 2.5mm2 |
|---|
| Mounting position | Any |
|---|
| Protection degree housing | IP40 |
|---|
| Protection degree conntector | IP20 |
|---|
| Temperature range | 0°C to 65°C |