Descripion | LSE-D16-BS Operation-/Fault indicator |
---|
Part number | LSE-D16-24-BS |
---|
Communication | 16 Multicolour-LEN / integrated Buzzer |
---|
Operation inputs | 16 inputs NO/NC each input separate |
---|
Fault inputs | 16 inputs NO/NC each input separate |
---|
Delay times for fault inputs with virtual DIP switch | 5s/10s/60s for all fault inputs collectively |
---|
Delay times for fault inputs with web interface | 1s to 48h for each fault input separately |
---|
Time delay fault inputs | 5s/10s/60s for all fault inputs, global |
---|
Automatic alarm acknowledgement after energising | 5s/10s/60s for all fault inputs, global |
---|
System imputs | External Horn acknowledgement / External Lamp acknowledgement / External Lamp test |
---|
System outputs factory settings | Horn until HQ / Common / Lamp test activated for 5s |
---|
Outputs alternative | Horn acknowledgement activated during keystroke on HQ / Lamp acknowledgement activated during keystroke on LQ / Common Priority 2 |
---|
Switching capacity output relays | 6A 30VDC / 6A 250VAC |
---|
Front control elements | Horn acknowledgement / Lamp acknowledgement / Lamp test |
---|
Supply voltage | 8-30VDC / 12-28.5VAC, 40-80Hz |
---|
Signal voltage | 24V AC/DC ± 20% |
---|
Power consumption | Max. 3W |
---|
Weight | 260g |
---|
Dimensions | WxHxD 72x144x75mm |
---|
Front panel cut out | 138x68mm |
---|
Connectors | Plug-in screw terminals 0.2 - 2.5mm2 |
---|
Mounting position | Any |
---|
Protection degree housing | IP40 |
---|
Protection degree conntector | IP20 |
---|
Temperature range | 0°C to 65°C |