Description Function Technical data Schematic Dimensions Order overview Downloads |
||
Three phase current monitoring relay 900CPR-3-1 |
Description
Digital three phase current monitoring relay from Selec with LCD display.Monitors overcurrent, undercurrent and assymetry with RMS measurement.
Easy setting with three front push buttons with sealable cover. Slim space saving design, only 35mm wide. 35mm DIN Rail mount.
Function Please click on the image for a larger view
Technical data
Display | |
---|---|
LCD | 3 digit liquid crystal display with backlight |
Input | |
Measurements | Undercurrent, Overcurrent, Asymmetry |
Time settings | Power ON delay, Trip time delay, Recovery time delay |
Alarm indications | Trip |
Latching | Selectable |
Reset | Auto / Manual (selectable) |
Electrical connection | 1,2,3 Phase |
Supply voltage | 230VAC ±15% |
Frequency | 45 - 65Hz |
Power consumption | 15VA max. |
CT Settings primary | 1A/5A - 999A (selectable) |
CT Settings secondary | 1A / 5A (selectable) |
Measuring range (RMS Value) | 0 - 1,19kA |
Trip settings undercurrent | 0 - 999A |
Trip settings overcurrent | 0,5A - 1,19kA |
Trip settings asymmetry | 5 - 99.9% |
Power ON delay | 0,5 - 99,9s |
Trip time delay | 0 - 99.9s |
Recovery time delay | 0 - 99.9s (in auto reset mode) |
Response time | <200ms |
Hysteresis current | 0,1 - 99,9A |
Resolution current | 0,01, 0,1, 1A, 0,01kA (depends on CT setting) |
Accuracy current | ±1% of setting ±2 digits |
Accuracy time setting | ±5% of setting ± 200ms |
Output | |
Contact | 1 SPDT (1 C/O) |
Relay rating NO | 5A @ 250V AC |
Relay rating NC | 3A @ 250V AC |
LED1 (red) | Relay (continuously ON after trip) |
Environmental specifications | |
Operating temperature: | 0 - 50 C |
Storage temperature | -20 - 70 C |
Humidity | 95% rF (non-condensing) |
Pollution gegree | 2 |
Mechanical specifications | |
Dimensions wxhxd | 35 x 90 x 70.5mm |
Mounting | 35mm DIN rail |
Weight | 130g |
Protection degree terminals | IP20 |
Protection degree housing | IP30 |
Protection degree faceplate | IP50 |
EMC | |
Electromagnetic compatibility | IEC61326-1 |
ESD immunity | IEC61000-4-2, Level 3 |
Surge immunity: | IEC61000-4-5 +/- 2kV common mode, +/- 1kV differential mode |
Radiated susceptibility: | IEC 61000-4-3 Level 3, 80 - 1000MHz |
Conducted Susceptibility | IEC61000-4-6, Level 2 |
Voltage dips and interruption: | IEC61000-4-11, Level 3 |
Conducted emissions | CISPR11 & IEC 61000-6-3 |
Radiated emissions | CISPR22 |
Electrical fast transient | IEC61000-4-4, Level 3 |
Schematic
Please click on the image for a larger view
Dimensions
Please click on the image for a larger view
Order overview
Order number | Designation | Appendage | Stock*1 | Price*2 | ||
---|---|---|---|---|---|---|
900CPR-3-1 | Stromüberwachungsrelais 3Phasen | 0.1 -999A / 230VAC / 1x UM | 1 | 144.50 CHF |
*1: Stock levels are for reference only. The handout is done upon incoming orders. |