TS200 OM 24 output module |
Digital outputs Signal level without load: Signal = 0 Signal = 1 Signal = 1, I = 0.5A, US = 24V DC Output current (signal =1) Short-circuit current Switch-off time Restart time after short-circuit Total loading capacity Minimum switching current Limitation of inductive switch-off voltage Switching frequency: Ohmic load Inductive load Consequence of overloading |
8 (FET, positive switching) max. +2 VDC +18 to +36 VDC +23 VDC 0.5 A typ. 5 A 1.5 msec = 5 sec 4 A 100 ÁA self-induction recuperation diode 100 Hz 2 Hz unit may be destroyed |
Bus connection |
CAN (ISO 11898) |
UB power supply Operating range Limits Power consumption: Without IE / OE Full configuration |
+24 VDC NOM +18 to +36 VDC -36 to +36 VDC max. 2.1 W max. 9 W |
Power supply US Operating range and limits |
+24 VDC NOM +18 to +36 VDC |
Electrical isolation Supply / Logic and Bus Output / Logic and Bus Output / Input |
yes yes no |
Ambient temperature Operating Storage |
0 to +55 ¦C -25 to +70 ¦ |
Protection category |
IP 40 |
Dimensions (W x H x D) in mm | 100 x 58 x 85 |
Weight |
220 g |