Display | |
---|
LCD | 3 row, Liquid Crystal Display with backlight |
---|
Digits | Row 1 with 4 digits, row 2 and 3 with 7 digits |
---|
LED | Integration of energy (1000 pulse /kWh) |
---|
Input Specifications | |
---|
Electrical connection | 3Ø - 3 wire, 3Ø - 4 wire, 2Ø - 3 wire, 1Ø - 2 wire |
---|
Input voltage range | 19 - 519V AC (L - L), 11 - 300V AC (L - N) |
---|
Frequency | 45Hz - 65Hz |
---|
Measuring Parameters | |
---|
| Voltage (L-L/L-N) (individual / average) |
---|
| Current ( 1, 2, 3) (individual / average) |
---|
| Frequency, power factor (individual /average) |
---|
| Active, reactive, apparent power (individual / total) |
---|
| Active, reactive (import / export) |
---|
| Minimum / maximum reactive power |
---|
| Maximum apparent power |
---|
Display reset | Programmable (for energy) |
---|
Resolution energy | 0,01k, 0,1k, 1k, 0,01M, 0,1M, 1M (depending upon CT ratio X PT ratio) |
---|
Resolution voltage, current, power | Auto resolution |
---|
Resolution power factor | 0.01 |
---|
Resolution frequency | 0.1Hz |
---|
Accuracy voltage (L-N/L-L), current | ±0,5% of full range |
---|
Accuracy power factor | ±0,01 |
---|
Accuracy frequency | ±0,1 % (for V>20 L-N, V>35 L-L) |
---|
Accuracy power (kW, kVA, kVAr) | 1% |
---|
Accuracy energy (active, reactive, apparent) | 1% |
---|
Memory retention | 10 years (for energy) |
---|
Overload rating | 20% continuous over load and able to withstanding 20 times the normal current rating for a period one second. |
---|
Overvoltage rating | Accept input voltage upto 120% of the nominal voltage |
---|
Power consumption | 8VA max. |
---|
Output Specifications | |
---|
Communication | RS485 MODBUS RTU communication |
---|
Supply specifications | |
---|
Auxiliary | 85 - 270V AC (50/60Hz) |
---|
Isolation | I/P, O/P and Aux. circuits isolated from each other and earth ground. |
---|
Resettable Parameters | |
---|
C.T primary | 5A to 10kA programmable for any value |
---|
C.T secondary | 1A / 5A |
---|
P.T primary | 1 V to 500kV programmable for any value |
---|
P.T secondary | 100V to 500V (L-L) programmable for any value |
---|
Environmental Specifications | |
---|
Operating temperature | -5 to +60 C |
---|
Storage temperature | -20 to +75 C |
---|
Humidity | up to 85% (non-condensing) |