Description Features Block diagram Schematic View Technical data Order overview / Versions Downloads |
||
| Temperature Converter PXT-10/11 | ||
Description
Temperature converter for converting a temperature to an analogue process signal. The temperature converter has an Pt100/Pt1000 input in two ranges -50-300°C and -50-100°C. A typical application is where temperature measurement is required and when a PLC/ Controller only has analogue inputs. The temperature range for input and type of analogue output are selected via choice of terminal - see connection diagram.Features
- Pt100/Pt1000 probe input with/without compensation for cable resistance in two ranges -50 to 300°C and -50-100°C- Output 0-10VDC/0-20/4-20mA - selected via terminals
- Output offset and gain adjustable ±5%
- LED indication of input less than 5%
- Galvanically isolated supply/output is 3,75kV AC 1 min
- Operating voltage 24VDC, 24VAC, 115VAC or 230VAC
Block diagram
Schematic
View / Size
Technical data
| Input signal |
Pt100/Pt1000 probe (DIN43760/IEC751) 2 or 3 wire with compensation for cable resistance |
|---|---|
| Temperature range | -50-300°C -50-100°C |
| Output (selected via terminals) | 4-20mA DC 500 Ohm 0-20mA DC 500 Ohm 0-10V DC via intern 500 Ohm shunt |
| Linearity | lower than 0,05% of full scale. |
| Mounting | 35mm DIN-rail |
| Terminals | Screw terminals up to 2x 2.5mm2 |
| Supply voltage | Version 924= 24VDC (20.4-27.6V DC) Version 024= 24VAC (20,4-27,6V AC) Version 115= 24/115VAC(20.4-27.6/98-132VAC) Version 230= 24/230VAC(20.4-27.6/196-264VAC |
| Frequency | 45-66 Hz |
| Power consumption | AC: 3VA / DC: 2W |
| Electric isolation | 3.75kVAC |
| Temperature range | -20 - +55°C |
| Protection degree | IP 20 |
| Weight | 170g |
Order overview / Types
Standard Stock Types
Description