Description Features Block diagram Schematic View Technical data Order overview / Versions Downloads |
||
| Threshold relay PXL-10 | ||
Description
A threshold relay for the monitoring or control of common types of process signals. The process signal to be monitored is selected on the front panel and the threshold value isalso adjusted via a setpoint potentiometer on the front of the relay. As the input signal attains the threshold plus the hysteresis the output relay energises. When the input signal drops and passes the threshold, minus hysteresis, the relay de-energises. The hysteresis is adjustable on the front, ±0,5 - 20%. By strapping 2 terminals, the relay can be inverted. A red LED indicates if the relay is energised. There is also a latch function where the relay after energising will remain energised, regardless of input, until the latch jumper or the operating voltage is disconnected. Typically used in safety circuits.Features
- Input 0 - 5V/0-10V/-10-+10VDC/0-20/4-20mA in one version- Adjustable setpoint
- Hysteresis adjustable ±0,5-20%
- Automatic locking (Latch)
- Inversion of relay function
- Output SPDT
- Operating voltage 24VDC, 24/115VAC or 24/230VAC
Function diagram
Schematic
View / Size
Technical data
| Input signal | 0-5V DC 0-10V DC -10 - +10V DC 0-20mA DC 4-20mA DC |
|---|---|
| Impedance | Voltage 100kΩ / Current 50Ω |
| Delay | under 20mS |
| Output relay | 1 C/O |
| Electrical life | Min. 3 x 107 operations with full load. |
| Mounting | 35mm DIN-rail |
| Terminals | Screw terminals up to 2x 2.5mm2 |
| Supply voltage | Version 924= 24VDC (20.4-27.6V DC) Version 115= 24/115VAC(20.4-27.6/98-132VAC) Version 230= 24/230VAC(20.4-27.6/196-264VAC) |
| Frequency | 45-66 Hz |
| Power consumption | AC: 3VA / DC: 2W |
| Electric isolation | 3.75 kVAC |
| Temperature range | -20 - +55°C |
| Protection degree | IP 20 |
| Weight | 180g |
Order overview / Versions
Standard Stock Types
Description