3-Phase monitoring relay MXP-20





Description

A relay for monitoring a 3-phase AC power supply with or without Neutral. The relay monitors that all phases are available and in the correct phase sequence L1, L2, L3 (U,V,W), that none of the phases are shifted more than 20° in relation to each other and that one or more of the phase voltages are not too low. When all three monitoring criteria are fulfilled the relay is activated. If one or more of the criteria are not fulfilled the relay de-energises and a red LED indicates failure. Fixed limits for energizing and de-energizing the single output relay. With connection of Neutral the measuring abilities are optimal, as Neutral works as a measuring reference. Without Neutral, the phase monitoring relay generates a Neutral reference from the connected phases.


Features

Monitoring of:
- Phase rotation
- Phase shift less than 20°
- Low voltage
- Output SPTD.
- Operating voltage via phases L2 and L3 (V and W).
- Delay= 0,5s to prevent faulty energization and deenergization caused by short interferences.



Function diagram


Voltage monitoring
Funktion



Phase monitoring
Funktion




Schematic


Wiring MXP20




View / Dimensions


View Brodersen MXP-20




Technical data

Input signal 3x150 / 3x230 / 3x400 VAC+N
Frequency 45-66Hz
On delay 0.3-0.7s
Output relay 1 NO/NC
Switching frequency Max. 1000 operations per hour with full load
Electric life span Min. 3x107 operations with full load
Mounting 35mm DIN-Rail
Connectors Max. 2x 2.5mm2 screw terminals
Supply voltage V(L2) and W(L3)
Power consumption 3VA
Ambient temperature -20 - +55°C
Weight appr. 180g



Order overview / Versions


Versions MXP 20